Images are for reference only and may show a similar model or a different version. Please verify the exact part number and specifications before ordering. Contact us for actual photos.
Rockwell Automation(Allen-Bradley) ControlLogix plc module 1756-RM2 or 1756RM2 technical datasheet/specification:Redundancy Module.
Rockwell Automation(Allen-Bradley) ControlLogix plc module 1756-RM2 or 1756RM2 technical datasheet/specification:Redundancy Module.
ControlLogix 5580 and ControlLogix 5570 Redundant Controllers
ControlLogix 5580 and ControlLogix 5570 controllers support controller redundancy. In a redundant controller system, you need these
components:
• Two 1756 chassis, each with the same of the following:
- Number of slots
- Modules in the same slots
- Redundancy firmware revisions in each module
- Approved module firmware revisions for use within ControlLogix Redundancy systems.
• One 1756-RM2 or 1756-RM2XT module per chassis that supports the following:
- One or two ControlLogix controllers of the same family. ControlLogix 5580 controllers support redundancy with the
Studio 5000 Logix Designer application, version 33 or later.
- For ControlLogix 5580 controllers, as many as seven EtherNet/IP communication modules.
- For ControlLogix 5570 controllers, as many as seven ControlNet or EtherNet/IP communication modules in any combination.
• One or two 1756-RMCx cables
If you want user manual of the 1756-RM2,please contact us for help.