Images are for reference only and may show a similar model or a different version. Please verify the exact part number and specifications before ordering. Contact us for actual photos.
The 1734-AENT/1734-AENTR adapter supports direct-, rack-, and
enhanced rack-optimized connections. A direct connection is a real-time data
transfer link between the controller and whatever module occupies the slot
that the configuration data references. Direct-connection messaging occurs at
a cyclic rate specified by the requested packet interval (RPI) during
configuration. A rack-optimized connection is a grouping of data from more
than one digital I/O module into a single block of data sent over a single
connection at the same data rate. Rack-optimized connections reduce the total
number of connections needed to transfer data when using many digital I/O
modules in a system.A total of 63 POINT I/O modules can be assembled on a single
EtherNet/IP node.
Expansion power supplies may be used to provide additional POINTBus
backplane current.
See the User Manual to determine the ratings for direct and rack
connections allowed.
Feel free to ask any questions about this product.